5.1 GENERAL
The a.c. motors throughout all offshore and onshore
installations are almost exclusively of the induction type, with squirrel-cage
rotors. They may be of high voltage
supplied from HV busbars, or they may be of low voltage supplied from one or
other of the LV busbars; the latter form the great majority of offshore and
industrial motors.
The range of powers, extends from about 1 2000 hp
(9 000kW mechanical) down to 1 hp or even less. Motors below about 300 hp (220kWm)
run from the 440V or 415V system, but those of higher power are usually of the
high-voltage type.
When a motor is started direct-on-line (‘DOL’ starting),
at the instant of switch-on the rotor is stationary, and the motor behaves as a
short-circuited transformer. The initial
starting current at standstill is therefore very large, though at low power
factor. Typically it may be four to six
times the normal full-load current, with a power factor of the order of 0.3 to
0.2.
FIGURE 5.1
INDUCTION MOTOR CURRENT, TORQUE AND POWER FACTOR/SPEED CURVES
Figure 5.1 shows the varying conditions as a motor runs
up from standstill to full speed. As the
motor begins to move and to generate back-emf, the low power factor reactive
current steadily falls off, but the motor begins to draw more active power as
it accelerates. The net effect is that
the initial starting current persists fairly constant through most of the
run-up period, but the power factor steadily improves. Finally the speed settles down to just below
synchronous, that is with a small ‘slip’, and the current falls sharply to
whatever the load demands. This is
indicated as current/speed (blue) and power factor/speed (green) curves in
Figure 5.1, which also shows the characteristic ‘Rock of Gibraltar’
torque/speed (black) curve.
With very few exceptions all offshore motors are
direct-on-line started, whether of the high-voltage or low-voltage type. The 440V or 415V motors, which form the great
majority, are usually remotely started through contactors in separate panels of
LV switchboards (also called ‘Motor Control Centres’ or ‘MCCs’), which are
described in greater detail in the manual ‘Electrical Distribution Equipment’,
Part ‘A’. HV motors are remotely started
through circuit-breakers or vacuum or air-break contactors backed by High
Rupturing Capacity (HRC) fuses in HV switchboards.
The run-up time of a direct-on-line started motor
depends on:
·
The
starting torque of the motor
·
The
inertia of the driven load
·
Whether or
not the driven end is loaded.
Motors are designed for different starting torques. The 60% of Figure 5.1 is only typical, but
the range is much wider, depending on the application. In general, a high starting torque gives a
lower efficiency.
Clearly the inertia of, say, a centrifugal fan is far
less than that of a motor generator set, and the run-up time would be much
shorter. Loading the driven end (as
distinct from starting light) will clearly extend the run-up time.
Torque depends on the square of the applied
voltage. Therefore an induction motor is
very sensitive to voltage drop at its terminals, however caused. For example, a 20% drop in applied voltage
(i.e. to 0.8 nominal) will result in only 64% (0.82) of the designed
torque. In extreme cases this may prevent a motor from even starting at all,
especially if there is much breakaway friction (‘stiction’), as with
reciprocating drives. This is further
discussed in Chapter 6.
5.2 REDUCED VOLTAGE STARTING
If it is desired to reduce the heavy starting current to
a level well below that which would be experienced with direct-on-line
starting, various methods are available which reduce the voltage applied to the
motor at the instant of starting, and restore it to full value when the motor
has run up to speed. Two of the
principal methods are described below.
It should be noted however that reduced voltage starting also means
reduced starting torque, so that, where high starting torques are needed, these
methods may not always be suitable.
5.2.1 Star/Delta
Starting
Figure 5.2(a) shows the conventional method of starting
a motor direct-on-line.
Figure 5.2(b) is known as ‘star/delta’ starting. All six ends of the motor windings are
brought out, and a 3-pole changeover hand-switch or contactor connects them
alternatively in star or delta. (The
changeover switch is not, of course, inside the motor as indicated in Figure
5.2(b), but it is shown there for electrical clearness.) It is drawn in the ‘star’ position; delta is
the running condition, where full line voltage is placed across each phase
winding. When starting, the motor is
temporarily connected in star, so that the voltage appearing across any one
phase winding is line voltage divided by √ 3 (see the
inserts). Thus a 440V machine would have
254V applied to each phase - this is the ‘reduced voltage’ - and the starting
line current taken at that voltage is reduced to one-third of what it would
have been with a delta connection. When
the motor is up to speed and the starting current has fallen to its running
value, the motor is reconnected into delta and takes its full voltage across
each phase. As it is then running at
nearly synchronous speed, the changeover will cause only a small increase of
current.
FIGURE 5.2
STAR/DELTA STARTING
The changeover from star to delta may be by hand
changeover switch; it must be provided with an interlock to prevent it
operating until it has been returned to the star position. The star and delta positions are usually
tallied START and RUN respectively.
Alternatively the reconnection may be by contactor, especially with an
auto-started motor. Interlocks will
ensure the correct sequence of operating.
Delta-connected motors are less easy to protect than star-connected
ones and are little used on offshore installations. Consequently star/delta starting is seldom
found offshore but is very common in industrial installations, in which case
the machines run as delta-connected motors.
5.2.2 Auto-transformer
Starting
Figure 5.3 is a different form of reduced voltage
starting which uses an auto-transformer to provide the lower starting
voltages. (An ordinary double-wound
transformer could be used, but, as the ratio is close, an auto-transformer is
just as effective and is smaller and cheaper.)
FIGURE
5.3
AUTO-TRANSFORMER
STARTING
Here the motor is started on the
auto-transformer tap (typically 50 to 70%).
It runs up on the reduced voltage, taking an appreciably lower starting
current. When it is up to speed the
auto-transformer and its tap are disconnected by a hand-switch or contactors
and the motor is connected directly across the full-voltage mains. As in the case of star/delta starting, the
motor will be running at nearly synchronous speed at the end of the first
auto-transformer stage, so that the changeover to full voltage will cause only
a small increase of current. This
method, unlike star/delta, allows a star-connected motor to be used.
As with direct-on-line starting,
the run-up time depends on the motor design, on the inertia of the driven end
and on whether the machine starts loaded or light. In the case of auto-transformer starting it
will also depend on the voltage ratio of the auto-transformer and hence on the
voltage applied during the first stage.
Certain features of
auto-transformer starting should, however, be noticed:
(a) The ‘start’ and ‘run’
switches, if of the contactor type, must be positively interlocked so that both
cannot be closed at the same time, otherwise part of the auto-transformer
primary will be shorted out.
(b) The changeover from ‘start’
to ‘run’ must be time-delayed. When power is taken off a large running motor,
it remains magnetised for a time by its rotor current until it has been damped
out. While it continues, the motor will
be generating back-emf. If the full
voltage is applied while this is happening, it might come in anti-phase, with
consequent currents of the order of a short-circuit. Time delays of about two seconds are usual
with large motors.
FIGURE 5.4
KORNDORFFER METHOD
5.2.3
Korndorffer Method
The disadvantages are overcome by a
modification to the basic auto-transformer method, known as ‘Korndorffer’
starting, shown in Figure 5.4.
Here the auto-transformer remains
constantly connected, but it is not actually energised - that is, it does not
carry any current - until its star-point is completed by a circuit-breaker or
contactor. As soon as the main breaker
and star-point breakers are closed, the motor, which is permanently connected
to the auto-transformer taps, receives its reduced voltage and starts its first
stage run-up.
When it is up to near synchronous
speed, the star-point breaker opens, leaving the motor still connected to the
mains through the auto-transformer primary section acting as a choke. Immediately after the star-point breaker has
opened, and without special time delay, the ‘run’ breaker closes, connecting
the motor direct to the full-voltage mains to complete its second stage and
shunting out the choke. At no time
during transition from first to second stage has the motor been totally
disconnected from the mains; therefore its back-emf can never become
out-of-phase with the mains voltage.
In large motors the sequence of
switch closing and opening is automatic and is tied in with other mechanical
sequences such as pre-start purging of the motor casing, running up of
lubricating pumps and correct opening of valves on the driven load side. The completion of each stage is monitored by
timing relays, and, unless it is completed within a certain preset time, the
main breaker is tripped and the start aborted, with appropriate alarm lamps lit
on the main control panel.
On most installations the only motors large enough to
require auto-transformer starting are typically those driving the Gas
Compression Pipeline Boosters and Re-injection Compressors. On Brent ‘A’, ‘B’, ‘C’ and ‘D’ these motors
are rated between 7 160kWm and 9 250kWm
(9 600 hp and 12 400 hp) and are started using Avon (18MVA)
generators as supply source and in each case the Korndorffer method is used
5.3 EFFECT ON SYSTEM OF STARTING A LARGE MOTOR
One very important consequence of starting these very
large motors must be realised. Even with
reduced voltage starting and the consequent limiting of the starting current,
the call on generator capacity is considerable.
Because the starting power factor is low, most of the starting current
is reactive, at least at first, and it is shown in Chapter 3 of the manual
‘Electrical Generation Equipment’ that it is the reactive load current which
causes voltage drop in generators. In
the case of the 9 250kWm re-injection compressor motor the
reactive starting load is about 23Mvar, which is more than one generator, even
of Avon size (18MVA), can reasonably cope with.
At least two generators should be on line to enable such a motor to be
started, and even then their AVRs will be extended to the limit to maintain
voltage. The situation will be
aggravated if the generators already have an appreciable standing load, and
load-shedding may be found necessary to enable a start to be made.
In the extreme case the voltage dip even with full AVR
action may be so great, and the starting torque so heavily reduced, that the
motor may not be able to break away against its ‘stiction’ and the motor may
fail to start at all.
In any case a severe voltage dip on the whole offshore
installation system may be expected until the motor is up to speed, and that
very dip may itself cause the motor to be sluggish in running up even if it
does not prevent it. If the dip is large
or prolonged, other motor contactors may trip on undervoltage, and operators
must be prepared to find this. Those
installations with only two Avons will be more susceptible than those with
four.
FIGURE
5.5
STARTING OF LARGE MOTOR
Figure 5.5(a) is an example of such a situation, and
Figure 5.5(b) shows the voltage situation at the motor terminals when a large
motor is direct-on-line (i.e. single-stage) started while another is running.
It is assumed that the AVR is already compensating for all other running loads,
including that of the large motor which is already running.
In the example shown, at the instant of start and before
the AVR can react, there is a sudden voltage drop of 30% due partly to the
reactive starting current flowing through the generator reactance and partly to
voltage drop in the feeder cable. This is followed by a short period of partial
recovery of about half a second while the AVR reacts and increases excitation
to the limit; the voltage rises somewhat but stays at 15% dip during most of
the run-up period because of continuing voltage drop in the cable. When the
motor is up to speed and its current falls to its ‘run’ value, the voltage
rises further as the cable drop is reduced until it settles at its controlled
value near 6.6kV. The voltage at the motor terminals, however, will still be a
little down (typically 2¼%) because of the voltage drop in the feeder cable due
to the motor’s running current.
Note that the intermediate drop level (15% in Figure
5.5(b)) to which the voltage partially recovers under AVR action will depend on
the standing load and the extent to which the AVR is already committed. The
amount and speed of recovery will depend on the margin left in the AVR.
It must be stressed that it is the reactive loading on
the generators due to the motor starting which is the critical factor. The
active (MW) load demanded by the gas compression motors during starting is well
within the capacity of one Avon unless it is already heavily loaded. When
shedding loads, therefore, those with large reactive components (e.g. motors)
should be selected rather than, say, heating. The Mvar meter on the switchboard
is the one to watch.
The whole question of how far a generator may be loaded
by running motors, or by motors which are about to be started, is discussed
more fully in Chapter 2 of the manual ‘Electrical System Control’ under the
heading ‘Capability Diagram’.
Starting a large motor in an extensive onshore
installation, which is backed up by a big supply network, is less of a problem;
the principles set out above remain, although their effect may be less
noticeable.
5.4 REPEATED STARTING
If, when a start signal is given, a
motor does not start, there is an understandable urge to ‘try again’.
Each time an attempt is made to
start a motor and the contactor actually closes but the motor does not move, a
severe starting current of the order of five to six times full-load current
flows continuously through the contactor contacts and the windings of the
stationary motor. This gives rise to heating (I2R) at a rate 25 to 36 times normal for
the motor, and without ventilation. When in due course the overcurrent
protection operates and trips the contactor, not only has a large amount of
heat been generated inside the motor, but also the contactor has to break some
500% of the normal current, and at a low power factor - a most severe
condition.
If another attempt is made
immediately, the overcurrent protection resets. It has the same time delay as
before, and therefore an equal amount of heat is released to be added to the
first. Each starting attempt will therefore raise the motor winding temperature
still further. Too many attempts will raise it to such a temperature that there
is severe risk of damage to the insulation and of an immediate or early
breakdown, even though the protection is working properly. Cables and motor
cable boxes may also be thermally overstressed, with similar risk of breakdown.
The repeated opening of the
contactor under such severe conditions is likely not only to overheat it but to
burn, and possibly weld, the contacts.
Many examples of this have been reported. If this happens and the contactor cannot open
because of welding, all protection of the motor is lost, and a burnout is
almost inevitable, and possibly fire.
Some motors are now provided with
thermistor or resistance thermal detector elements embedded in their
windings. They detect the temperature
rise from whatever cause and, if it exceeds a certain preset level, they trip and lock out the motor until it has
cooled (always assuming, of course, that the contactor has not welded-in). The operator can seldom know whether any
particular motor is so protected, and he should observe a general rule that if,
after two attempts, a motor does not start, he should make no further try but
call in Maintenance.
Indeed some operators have laid
down a general instruction that motors over 50kW are only suitable for two
successive starts when cold.
Another one start attempt is allowable after a cooling period of 30
minutes at standstill. No more than
three starts may be attempted in any one hour.
For certain very large motors the
manufacturers may make special stipulations not only on the number of starting
attempts, but also on the maximum permitted number of successful starts over a
given time. For example, for the large
gas compression motors (7.1MW to 9.2MW) they stipulate not more than two attempted
starts in succession, not more than one successful start in any 30 minutes and
not more than 300 starts in one year.
5.5 EXAMPLE OF A MOTOR STARTING CALCULATION
At the end of Chapter 4 a calculated example was given
on how to estimate the current and power taken by a motor when running
at various loads. Now an example is
given of the calculation needed to estimate the current and power (active and
reactive) of a motor when starting. The
same motor as was assumed for the Chapter 4 example is used, but certain
additional starting information is given, such as would be found on the motor’s
rating plate.
Starting current = 182A (36A)
Starting power factor = 0.2 (0.8)
Starting active power = 416kW (333kW)
Starting reactive power = 2 040kvar (250kvar)
If these four figures are compared
with the corresponding quantities in the top line of the table of Chapter 4 for
the motor running on full-load (repeated above in brackets alongside each), it
will be seen that, when starting:
(a) The starting current is very much
greater (it was given as 5 times).
(b) The starting power factor is very much
lower (it was given as 0.2).
(c) The starting active power is of the same
order as the full-load running active power (in this case a little higher).
(d) The starting reactive power is vastly
greater than the full-load running reactive power (in this case eight times).
As the motor runs up and approaches
synchronous speed, these figures gradually change until, at whatever load the
motor is to run, they settle at the figures in the table of
Chapter 4.
Chapter 4.
Since the voltage drop in a
generation and distribution system is due principally to the reactive loading,
it becomes clear that a voltage dip will be experienced whenever a motor,
particularly a large motor, is started. The sudden demand for considerable
reactive power will cause the voltage to drop before the AVR is able to correct
it. This appears on an installation as a momentary dip of the lights.
Thank you so much for this information. If you are looking for Transformers Manufacturers in Pune , You may visit Trutech Products, One of the best Transformer Manufacturers in India.
ReplyDeleteThanks for sharing this informative post with us.
ReplyDeleteIf you are searching Best Transformer Manufacturers in India, and want to buy any kinds of Transformers so, Trutech Products is one of the prominent Transformer Manufacturers In Mumbai.
Transformer Manufacturers in Pune