ReplyDeleteI am looking for the following information
ReplyDeleteVoltage Ur (kV)
BIL Up (kVp)
Rated Current Ir(A)
Rated Short Circuit Breaking Current Isc (kA)
Rated Short Circuit Making Current
Ima (kAp)
Rated Short Time Withstand Current (Momentary Current) (Ik) kA
Rated Duration of Short Circuit
tk (s)
for the reclosers below
A) Type RV-McGraw-Edison
B) Kyle Recloser Type V4E - Cooper
C) Kyle Recloser Type KFVME - Cooper
D) Kyle Recloser Type KFME - Cooper
E) Type VERSAVACII-Joslyn Hi-Voltage Corporation
F) Reyrolle - England
I would appreciate it if you can send me the manuals with those data.
My e-mail adress are AprilAC@eskom.co.za
DEAR SIR,
ReplyDeleteTO AVOID MAJOR FAILURE WHAT IS THE MAINTENANCE/TESTING REQUESTED ON CCVT/CVT.
PLEASE KINDLY FORWARD.
dear sir,
ReplyDeleteplease furnish the recomended maintenance / testing on service ccvt/cvt.
hey Govindan Palanichamy,
ReplyDeletehere alot of basic service that should be done from time to other.
- CAUTION: BEFORE PERFORMING ANY TESTS ENSURE THAT UNIT HAS BEEN COMPLETELY DE-ENERGIZE
- confirm of Volt tap ground switch up all the time.
- Megger X and Y windings to tank should read 50 meg ohms or more. every while.
- Megger P2 to tank should read 50 meg ohms or more.
- Measure resistance from P2 connection to tank, should read less than 1000 ohms.
- Measure capacitance between CAR connection and basebox. This gives C2 value.
- Measure capacitance from top of capacitor to basebox. This gives C1 value.
- Measure P1 - P2, should read less than 75 ohms
- Check all connections Daily.
- Check harmonic suppression filter wiring and components, replace as necessary.
- Check for leaks around tank
- Check expansion chamber on top of lower capacitor unit
perform a regular
ReplyDeletevisual inspection of the following:
• Chipped porcelain
• Abnormal pollution accumulation
• Oil leaks
• Check oil level of the basebox by means of the oil
gauge.
I want to read turbine speed control by automatic governor chapter-5 please send to my mail id mahesh.petro15@gmail.com
ReplyDeleteI am looking for the maintenance manual for Mindray Anaesthetic machine
ReplyDeletemy email is : trychaga@gmail.com