6.1 GENERAL CONSIDERATION
Due to system disturbances, especially when starting large drives on limited generating capacity, motors may at any time find themselves operating on a voltage lower than the nominal value.
FIGURE 6.1
CURRENT AND POWER IN A
SIMPLE RESISTOR
If such a thing happened when
voltage were applied to a simple resistor, as shown in Figure 6.1, the current,
as determined by Ohm’s Law, would always remain proportional to the applied
voltage. For example, a 10% reduction of
voltage (i.e. to 0.9 times nominal) would result also in a 10% reduction of
current (i.e. to 0.9 times its previous value), and the power, which is the product of voltage and current, would be
reduced to 0.92, or 0.81, times its previous value - that is, a
power reduction of 19%. For small
voltage reductions the percentage power drop is approximately double the
percentage voltage drop.
This is quite simple with a fixed
resistance, but induction motors do not behave in this way, as will be
explained below. It is because they do
not present a fixed impedance to the voltage, equivalent to the R of Figure 6.1. In fact Ohm’s Law does not appear to
apply. The behaviour of motors when the
applied voltage varies must be examined in more careful detail.
6.2 EFFECT ON TORQUE
It was explained in Chapter 2 that an induction motor
operates by the interaction of the rotating stator field and the currents in
the rotor bars. The magnitude of the
field depends directly on the applied voltage; also the emf induced in the
rotor, and so the rotor bar current, depends on the strength of that
field. So the rotor current too depends
on the voltage, and, since the developed torque is the product of both, that
torque is proportional to the square of the applied voltage. Expressed in symbols:
T
ยต V2
It will be seen therefore that torque is very sensitive
to voltage variation. Taking the figures
from the previous example, a 10% reduction of voltage (i.e. to 0.9 times
nominal) reduces the torque to 0.92, or 0.81T. For small voltage
variations the percentage drop of torque, like that of the power, is
also approximately double the percentage voltage drop.
For small voltage variations this might be acceptable,
although it would increase the motor’s run-up time from starting and could so
cause some overheating. It can, however,
pose a serious problem if the variation is large. For example if, when starting a very large
motor, the system voltage fell by 30% (i.e. to 0.7 times nominal - a situation
not unknown), the torque would fall to 0.72, or 0.49T - that is, to about half its nominal
value. If this were the starting torque
of a large motor with a high-friction drive, it might not be enough to overcome
the initial break-away friction, or ‘stiction’, and the motor would then not
start at all.
Consider now the effect of a running motor suffering a
sudden reduction of applied voltage of 10% - that is, to 0.9 times nominal.
It has already been shown that the torque will be reduced by 19%, that
is to 0.81T.
FIGURE
6.2
INDUCTION
MOTOR OPERATING ON REDUCED VOLTAGE
The full lines of Figure 6.2 are
reproductions, on a wider scale, of the right-hand parts of the torque/speed
(black) and current/speed (blue) characteristics of Figure 5.1 in Chapter 5,
for a motor operating at its rated, or nominal, voltage. The dotted curves are the corresponding
characteristics for the same motor operating at a 10% reduced voltage. As already explained, the reduced-voltage
torque/speed curve will lie at all points 19% below the nominal curve.
Point S is synchronous speed and point N the actual
speed when a stated load torque is applied with the motor working at nominal
voltage. SN is then the slip, point P
the working point for the given load torque, and point Q the working current
point.
If now, while the motor is still loaded, the voltage is
reduced by 10%, momentarily the external load torque and the speed remain
unaltered. All that happens is that the
characteristics change suddenly from the full-line to the dotted-line curves,
and the torque working point drops from P to P”.
The torque being delivered by the motor (NP”) is now
less than the mechanical torque being imposed on it by the external load. Since the latter has not changed, the motor
and its driven load will begin to slow down, and the speed point will move to
the left from position N. The slip will
increase, and, as it does so, the working point will move to the left from P”
up the dotted characteristic. As it does
so the motor torque will increase. When
it reaches a new point P’, it is once again equal to the load torque; the
deceleration ceases and the motor settles down to a new speed N’ slightly less
than its previous full-voltage speed N, and with a slightly increased slip. The progressive change in torque is indicated
in Figure 6.2 in red.
6.3 EFFECT ON CURRENT
On the same Figure 6.2 the point Q represents the
current with full voltage applied and with the given load. After voltage reduction the new speed is at
point N’, and the new current is given by point Q’ on the intersection of the
vertical through N’ and the reduced-voltage dotted current curve. This is higher than the current (Q) at
full voltage - that is to say, the current rises as voltage is reduced, in
direct contrast to Ohm’s Law.
This result should not be surprising if considered from
the power point of view. The mechanical
power extracted from the motor is the product of torque and speed. The speed decreases only slightly since there
has been a slight increase in a small slip, and the load torque can be regarded
as almost constant. Consequently the
mechanical power output is also nearly constant, demanding a near-constant
electrical power input. But electrical
power (VI cos j) is
proportional to the product of V and I, so, if V goes down,
I must go up more or less in inverse proportion.
6.4 PULL OUT AND STALL
In Figure 6.2 the dotted torque curve was drawn for only
a 10% voltage reduction, and the maximum available, or ‘pull-out’, torque shown
there (point Z’) is greater than the load torque. Therefore a point P’ will be established
where the motor torque can rise to meet the demanded load torque, even with the
10% voltage reduction, and the motor settles down to a new steady but slightly
lower speed.
But if the voltage reduction had been greater, the
dotted reduced-voltage torque curve would be far lower (being proportional to V2),
and its maximum, or pull-out, value at point Z” might then be lower than the
demanded load torque, as indicated in part by the chain-dotted curve in Figure
6.2. The point P’ could then never be
found where the motor torque can rise to meet the load torque, and deceleration
would continue until the motor stalled to a stop. Its current would rise to its starting or
‘locked-rotor’ value at that voltage and would flow continuously, causing rapid
overheating (see Chapter 10, Paragraph 10.3, ‘Overcurrent / Overloading’). The motor would have to rely on its automatic
protection to clear it off the line and prevent burnout.
Even without a voltage reduction, if
the load torque should rise excessively - for example due to a malfunction of
the driven machine, or to a bearing seizure - to a level exceeding the pull-out
peak torque curve of Figure 5.1, the torque delivered by the motor cannot then
rise to meet it, and the motor will decelerate into a stall. The lower the voltage, the lower the pull-out
torque.
No comments:
Post a Comment