The
field instrumentation in process plants is beginning to come under more
sophisticated metrological discipline. Most new field instruments are now smart
digital instruments. One popular digital protocol is the HART (Highway
Automated Remote Transducer) protocol, which shares characteristics of both
analog and digital control systems.
To
properly service these instruments, precision analog source / measure
capability and digital communication are both required. Historically, this
operation has required two separate tools, a calibrator and a communicator.
Today, these capabilities are available in a single HART Documenting Process
Calibrator that can help technicians quickly and effectively service a HART
instrument workload.
Process
environment demands productivity:
Intense
competition in the Process Industries demands maximum output at minimum cost.
That productivity push extends into the maintenance department. At the same
time, regulations and quality standards are demanding more rigorous calibration
plus extensive documentation. Yet maintenance expenses are slashed to the
minimum. Most plants have responded by replacing analog instrumentation with smart
instruments. Smart is process jargon that describes any
microprocessor-based field device. The microprocessor offers extra
functionality, such as multiple sensor types, multiple measurement variables
(e.g. flow rate and volume), digital compensation, and temperature
compensation. These smart instruments generally offer better accuracy,
long-term stability, and reliability than conventional analog instruments.
Manufacturers
of field instruments have accelerated the changeover by offering smart
transmitters at prices approaching those of analog units. The majority of
installed instruments are now digital instruments. Most of these instruments
use the HART protocol.
What
is the HART protocol?
HART
stands for Highway Addressable Remote Transducer. The HART protocol uses 1200
baud Frequency Shift Keying (FSK) based on the Bell 202 standard 1 to
superimpose digital information on the conventional 4-20 mA analog signal.
Maintained by an independent organization, the HART Communication Foundation,
the HART protocol is an industry standard developed to define the
communications protocol between intelligent field devices and a control system.
HART
2 is the most widely used digital communication protocol in the process
industries, with over five million HART field instruments installed in over
100,000 plants worldwide. HART:
· Is supported by all of the major vendors
of process field instruments
· Preserves present control strategies by
allowing traditional 4-20 mA signals to co-exist with digital communication on
existing two-wire loops
· Is compatible with traditional analog
devices
· Provides important information for
installation and maintenance, such as Tag-IDs, measured values, range and span
data, product information and diagnostics
· Can support cabling savings through use of
multidrop networks
· Reduces operation costs, through improved
management and utilization of smart instrument networks
Calibration
is still required
Some
instrument shops have come to believe that the accuracy and stability of HART
instruments, plus the presence of instrument diagnostics, have eliminated the
need for calibration. Others believe that calibration can be accomplished by
re-ranging field instruments using only a HART communicator, either in the
field or from the control room. However, regular performance verifications with
a suitable reference standard are necessary because:
· Regulations governing occupational safety,
environmental protection, and consumer safety often require evidence of
traceable calibration for process instrumentation.
· Quality programs, such as ISO 9000,
dictate periodic calibration to recognized standards for all instruments that
impact product quality.
· Whenever weights, measures, and custody
transfer are involved, periodic calibration is required.
· Even with very long stated calibration
intervals, the performance of instruments will change over time. This shift may
be caused by long-term shifts in the transmitter electronics, or by exposure of
the transmitter and the primary sensing element to temperature, humidity, environmental
pollutants and vibration.
· Regular performance checks will often
uncover problems not directly caused by the instrumentation, such as solidified
or congealed pressure lines, or pressure lines that have become filled with
condensate.
· Other errors, for example installation of
a wrong thermocouple type, are often uncovered through periodic calibration.
How
are HART instruments calibrated?
Calibration
of an analog transmitter is fairly straightforward. Following an As-Found test,
the zero and span adjustments may be used to set the correct relationship
between the input signal and the 4 – 20 mA output. An As-Left test completes
the calibration.
A
HART instrument is more complex, having three distinct stages. The sensor input
stage sets the relationship between an input sensor and the PV, or primary
variable. The PV is denominated in engineering units, for example, psi or oF.
The Sensor Input stage is adjusted by digitally trimming using Sensor Trim. The
second stage is a computational stage, establishing the relationship between PV
(Primary Variable) and PVAO (Primary Variable Analog Output).
Range
is scaled by assigning the PV Upper Range Limit and Lower Range Limit values.
The PVAO is a digital value of the 4-20 mA output signal. The final stage, the
Instrument Output, is set digitally with Output Trim. Performing these trims
and entering the URV and LRV has typically been performed using a HART
configurator or communicator, such as the Fisher-Rosemount 268 or 275. A
separate calibrator was required to provide the precision analog source and
measure functions.
The
calibration approach for a HART instrument will depend on how the transmitter
outputs are used. If only the 4-20 mA analog signal is used, it may be treated
much as an analog transmitter.
Using
the manual zero and span buttons on the transmitter, or by digitally setting
the PV LRV and PV URV, the correct relationship between input sensor and 4-20
mA analog output are set.
However,
in this scenario, the Sensor Input stage has not been properly adjusted. If one
were to use a communicator to read the digital value PV, it will most likely be
incorrect, even though the
4-20
mA output will be correct.
If
any of the digital signals will be used by the control system, then a more
rigorous approach is required. If the PV will be used, then the input stage
must be correctly set using Sensor Trim.
Then
the PV LRV and PV URV should be digitally assigned, and never changed using the
manual zero and span buttons. Finally, the Output Trim is used to correctly set
the relationship between the PVAO and the 4-20 mA analog output. Holladay 3 provides
an excellent discussion on the proper calibration of HART devices.
Computation
New
tools speed calibration
It
is desirable to complete required calibrations as quickly and efficiently as
possible. In the past, maintenance of smart instrumentation was often done in
the shop. A benchtop calibrator was used for analog reference signals, and a
HART communicator or configurator provided the digital communication. Today,
most instrument maintenance is moving to the field. This reduces process
interruption and avoids the time and expense of removing the instrument to the shop.
Portable communicators and calibrators are often used together to complete
these field calibrations. However, the desire to carry as little equipment as
possible and to speed calibrations has created a need for a new class of calibration
tool. Today, the HART Documenting Process Calibrator combines calibration
capabilities and essential HART communication functions in one compact,
easy-to-use tool. With such a tool, one can quickly address a workload of both
HART and conventional instrumentation.
Via
the Service, Setup and Process softkeys, the Active Device Screen serves as a
portal to the entire HART feature set, as shown in the function tree below:
Saving
calibration time with an integrated HART calibrator
The
following examples demonstrate how a HART Documenting Process Calibrator can
shorten calibration times to help reduce maintenance costs.
1.
Easy hookup: Today, both a calibrator and communicator
are required, so hooking up the test takes longer. With the new integrated HART
calibrator, hook-up is much simpler.
Simply
connect the source and measure leads as you would for an analog transmitter.
Then, using the provided HART cable, connect the serial port to instrument
power input or the HART terminals.
2.
Fast acquisition of transmitter characteristics: With
today’s communicators, initialization and self-test can take 1-2 minutes. With
an integrated HART calibrator, simply press the “HART” key. Any connected
devices are automatically identified, typically within 10 seconds. If more than
one device is found (multi-drop configuration), simply select one of the found
devices to see the active device screen, Figure 1, above.
3.
Easy HART changes: Rather than calling up and then changing
individual functions, the HART calibrator uses simple, shallow menus to quickly
reach and edit key HART values.
From
the Active Device Screen, changes are quick and easy. For example, selecting
Setup and Basic positions you to easily edit HART variables such as Tag ID, PV
units, Upper and Lower Range Values.
4.
Automatic selection of analog mode source / measure setting:
With
a calibrator / communicator pair, calibrator functions must be selected and
entered by hand. With the integrated calibrator, from the active device screen
simply press the “HART” key to go to the analog mode. All appropriate source/
measure combination will be displayed, based upon the active HART device.
Simply pick an entry from the list.
5.
Automatic filling-in of test templates: With conventional
calibrators, test limits would be entered by hand. Then, tests would be
manually executed. With the HART calibrator, test procedure templates are
automatically completed. Measure and source limits are automatically filled-in,
again based on the presently connected HART device. Then, automated As-found
procedures are readily started.
6.
Automatic branching to adjustment choices: Once the
“As-Found”
test is completed, an Adjust softkey becomes available. Press “Adjust”. The
HART SERVICE screen automatically appears with appropriate selections for the connected
HART device. Simply choose from the list to automatically configure the
calibrator to execute the desired trim.
7.
Automatic entry of analog readings:
While performing digital trims per
observed analog measurements, no user entry of analog readings is required.
Readings may be captured with the Fetch softkey. Correct digital trim is then
accomplished simply by using the Send key to apply the fetched reading..
Guidelines
for selection:
A
technician’s typical HART workload is roughly 70% troubleshooting and
maintenance, 20% commissioning, and 10% calibration. In selecting a
HART-capable calibrator, one should look for a tool that can not only calibrate
but can extend to most of the daily troubleshooting and maintenance tasks.
In
general, that means insuring the tool can quickly interrogate and read
virtually all HART devices at the Universal command level. Specifically, one
should look for these capabilities:
· All of the necessary analog source /
measure functions
· Fast and easy HART communication, with no
programming knowledge required
· Loop power supply, including automatic
insertion of 250 Ohm resistor whenever loop power is enabled
· Full compliance with the Data Link Layer
of the HART protocol, addressing multiple masters, burst mode, and multi-drop
configurations.
· Extensive implementation of Universal,
Common-practice, and Device-specific commands
· A broad selection of supported devices
from a variety of manufacturers, e.g. ABB, Endress +Hauser, Honeywell, Moore,
Rosemount, Siemens, SMAR, and Yokogawa.
Conclusion
Using
one tool that integrates both calibration and HART communication capabilities
can greatly simplify and shorten the process of calibrating a HART field
device. This streamlining converts directly to increased technician
productivity and reduced maintenance costs.
No comments:
Post a Comment