2.1 GENERAL
The subject of ‘Switchgear’ is regarded as covering all
types of switching devices such as circuit-breakers, contactors and
hand-operated switches, as well as fuses and protective devices like relays.
Switchgear is used on both high-voltage and low-voltage
systems. It is required to enable
generators, feeders, transformers and motors to be connected to and
disconnected from the high-voltage or low-voltage system. This switching is necessary both for normal
operational purposes and for the rapid disconnection of any circuit that
becomes faulty. The switchgear also
allows any circuit to be isolated from the live system and for that circuit to
be made safe so that work may be carried out on equipment connected to it.
This chapter deals with switching devices as applied to
high-voltage systems; low voltage is covered in Chapter 3. Fuses and relays are dealt with in the manual
‘Electrical Protection’. Two types of HV
switchgear are considered in this chapter:
(a) Circuit-breakers
Circuit-breakers are used to control
generators, transformers, bus-sections, bus-couplers, interconnecting cables
between switchboards and the starting and running of very large motors; they
are designed to make and break full fault currents. A circuit-breaker may be of the oil-break,
air-break or vacuum-break type. Because
of the fire hazard only air-break and vacuum-break units are used on most
offshore installations, but oil-break circuit-breakers are widely used
onshore. They are not designed for
continuously repeated operation.
(b) Contactors
Contactors are used to control motor
circuits and sometimes transformers.
They may be of the air- or vacuum- break type; each type is used both
onshore and offshore.
Contactors are designed only to make and
carry fault current for a short time, not to break it. Where the system fault level exceeds the
limited breaking capacity of the contactor, fuses are inserted in series with
the contactor contacts. Contactors are
designed to undergo repeated and frequent operation without undue wear.
A switchboard may be made up of a mixture of
circuit-breaker and contactor cubicles, depending on the nature of the
individual loads and the distribution requirements.
A circuit-breaker or contactor has five ratings:
Voltage. This is the nominal system voltage at which
the switch will operate without breakdown.
Normal Current. This is the current which the switch will
carry continuously without overheating.
Breaking Capacity. This is the maximum fault current (expressed
in kA (rms) or MVA) which the switch will interrupt on all three phases.
Making
Current. This is the maximum peak asymmetrical
current (expressed in kA) that the switch can carry in any pole during a making
operation.
Short-time
Rating. This
is the maximum time (usually specified as 3 sec or 1 sec) for which the switch
will carry, without damage, the full fault current before that current is
broken.
The theory and manner in which the various types of
circuit-breaker and contactor extinguish the arc and interrupt the current is
dealt with fully in Chapter 1. The
descriptions which follow are concerned with the actual hardware, its operation
and its assembly into switchboards.
2.2 OIL CIRCUIT-BREAKERS (OCB)
In an oil circuit-breaker the contacts operate in a tank
of oil (sometimes in three separate but smaller tanks). There are usually two breaks in series per
phase, the moving contacts moving together in a downward vertical direction
inside the tank. Around each of the six
fixed contact tips is placed an arc-control device, usually of the ‘cross-jet
explosion pot’ type. A sectioned view
showing one phase of an OCB is seen in Figure 2.1, which shows the circuit-breaker
unit in its fixed housing and in the ‘Service’ position.
FIGURE 2.1
TYPICAL HIGH VOLTAGE OIL
BREAK SWITCHGEAR UNIT (VERTICAL ISOLATION)
The withdrawable truck is shown in blue, the main
copperwork, busbars and conductors red, and the oil is shaded yellow.
The circuit-breaker and its tank, with its six external
terminals (two per phase), can be withdrawn vertically downwards clear of the
corresponding plug-type connections in the main housing. When so withdrawn the circuit-breaker proper
is electrically isolated from the busbars and feeder, and automatic shutters
close over the six fixed live connections or ‘spouts’. Isolation may be
vertical (as in Figure 2.1) or horizontal.
After isolation the whole circuit-breaker unit in its tank, together
with its operating mechanism, can be drawn out clear of the housing
horizontally on its wheels for examination or maintenance.
Mechanical interlocks are provided to ensure that the
circuit-breaker unit can never be isolated unless it has first been opened, and
that it cannot be reinserted into the housing unless it is already open.
Where a panel is fitted with a voltage transformer (VT),
this is mounted in a separate compartment above the cable connection
compartment. In Figure 2.1 the VT is
oil-immersed in a tank, which can be withdrawn for isolation. A VT may be connected either to the feeder
side or to the busbar side of a circuit-breaker, depending on its application,
and it is protected by high-voltage fuses mounted inside the VT compartment (also
shown in Figure 2.1).
FIGURE 2.2
TYPICAL HIGH VOLTAGE OIL
BREAK SWITCHGEAR UNIT
ON DUPLICATE BUSBARS
(VERTICAL ISOLATION)
Operating mechanisms to close the
breaker may be solenoid, motor/spring, pneumatic or hydraulic and are described
more fully in para 2.3.3. The mechanism
must be strong enough to close the breaker positively against the ‘throw-off’
forces of the maximum short-circuit current that can possibly occur at the
point in the system where the circuit-breaker is installed (see the manual
‘Electrical Protection’).
Circuit-breakers latch-in when closed and are tripped by a separate
shunt-trip coil, always energised from an independent d.c. battery-supported source. In a few cases a no-volt coil is used for
tripping.
After clearing a full-scale fault an oil circuit-breaker
should be able to continue in operation without attention, but it is customary
to withdraw it at the first suitable opportunity to examine the contacts and
replace the oil.
Oil circuit-breakers, being usually large, are not often
made up into switchboards but are assembled into sets with common busbars
running through and, where possible, mounted out-of-doors. They are sometimes totally enclosed, with
their busbar system, in individual iron enclosures - the so-called ‘iron-clad’
or ‘metal-clad’ switchgear. The
controlling switchboard would be a separate unit indoors.
On some installations the switchboard contains two
independent busbar systems, and the circuit-breaker can be connected to either
set. This is the so-called ‘duplicate
busbar’ system.
A typical duplicate busbar arrangement, using vertical
isolation, is shown in Figure 2.2.
Selection between the rear and front busbars is achieved by moving the
circuit-breaker truck backwards or forwards to its correct position under the
rear or front pairs of fixed isolation contacts (or ‘spouts’). One set of spouts, the feeder connection, is
common to both rear and front sets. In
the figure the circuit-breaker is shown in the position to engage the front
busbars. When in position under the
selected spouts, the circuit-breaker is raised to make contact with the chosen
busbar system. Interlocks ensure exact positioning before the breaker is
raised.
Duplicate busbar systems may also be arranged for
horizontal isolation, but the vertical arrangement is more common. They are used more often with oil
circuit-breakers than with other types.
Duplicate busbar systems are fairly common in onshore
installations. They are also used on
some offshore platforms.
2.3 AIR BREAK CIRCUIT-BREAKERS (ACB)
2.3.1 Air
Break Circuit-breaker Panel
An air-break circuit-breaker panel is made up of two
parts: a fixed portion or ‘housing’ and a removable circuit-breaker truck. The precise layout varies from one
manufacturer to another; a typical arrangement is shown in Figure 2.3.
The unit shown in the figure is horizontally
isolated. The circuit-breaker truck
(blue) can be clearly seen in the ‘Service’ position with the breaker’s moving
contacts open and with the arc chutes above.
In this case the busbars run along the bottom of the housing, with the
feeder cable box at the back. The
busbars and other main copperwork are shown red.
The fixed part is divided into four compartments, each
one separated from the others by an earthed sheet-metal barrier. At the front of the panel are two
compartments; the upper one is a low-voltage compartment housing low-voltage
control equipment, associated fuses and auxiliary cable terminations. The lower one houses the circuit-breaker
truck. A door is fitted at the front of
each of the compartments. At the rear of
the panel are two further compartments each with a bolted cover. The lower compartment houses the busbars and
the upper the feeder cable terminations and current transformers, as shown in
Figure 2.3.
FIGURE 2.3
TYPICAL HIGH VOLTAGE AIR
BREAK SWITCHGEAR UNIT
(HORIZONTAL ISOLATION)
The circuit-breaker is mounted on a truck supported on
rollers which can be moved in a fore-and-aft direction within the
circuit-breaker compartment, or removed from it. At the back of the circuit-breaker
compartment are two steel shutters, one to cover the fixed feeder contacts and
the other the busbar contacts. When the
circuit-breaker is moved into the ‘Service’ position, the shutters open to
allow plugging contacts at the rear of the circuit-breaker to enter the
insulated spouts which house the fixed feeder and busbar contacts. The shutters provide a safety barrier to
prevent human contact with live metal when the circuit-breaker is disconnected
or removed from the panel.
Where a panel is fitted with a VT, this is mounted in a
compartment above the cable connection compartment. A voltage transformer may be connected either
to the feeder side or to the busbar side of a circuit-breaker, depending on its
application, and it is protected by high-voltage fuses mounted inside the VT
compartment (also shown in Figure 2.3).
The cover of this compartment can only be removed when the VT has been
isolated.
On the dead-front panel in front of the VT compartment
may be mounted indicating instruments, controls and the protective relays
concerned with that item of switchgear.
2.3.2 Air
Break Circuit-breaker Truck
A typical circuit-breaker on its
truck is shown in Figure 2.4. The
switching contacts are shown open, and above the fixed contacts are the arc
chutes. On the left are the two sets of
three isolating contacts, with their heavy contact tips, which engage with the
fixed busbar and feeder sets of isolating contacts in the housing. When the truck is withdrawn, safety shutters
drop to cover the live fixed contact spouts; these shutters are automatically
lifted as the truck is reinserted into the ‘Service’ position.
FIGURE 2.4
TYPICAL AIR BREAK CIRCUIT-BREAKERAND TRUCK
The motor/spring operating mechanism
is housed in the base. On the face on
the right-hand side (not seen in the figure) are the handle for manually
charging the spring, mechanical indicators for showing whether the spring is
charged or discharged, indicators for showing whether the breaker is open or
closed, and mechanical pushbuttons for releasing the spring (i.e. closing) and
for tripping the breaker; these are marked ‘l’ and ‘O’ respectively.
2.3.3 Operating
Mechanisms
The circuit-breaker closing
mechanism for either an oil-break or air-break circuit-breaker is usually
solenoid or motor/spring powered. The
solenoid uses d.c.,
usually at 110V, and operates on the breaker linkage. Alternative hand
operation is provided.
The closing mechanism operates through a toggle link
which, when closed, is ‘over-toggled’ and therefore solid. When a trip signal is given, a trip coil
breaks the toggle and allows the circuit-breaker to open under its trip
springs. If the breaker should be closed
onto a fault,
the toggle breaks immediately, so allowing the breaker
to re-open freely. This arrangement,
known as a ‘trip-free’ mechanism, protects the operator against injury by the
breaker’s throw-off forces if he unwittingly attempts to close it by hand onto
a fault.
A motor/spring mechanism charges a powerful helical
spring by motor. When charged, the
spring latches and remains so until released.
On receipt of a closing signal, the latch is released and the spring
closes the breaker through its linkage.
Immediately the breaker has closed, a limit switch causes the motor,
usually d.c.
operated, to recharge the spring ready for the next closing operation. In the event of motor power failing, the
spring can be recharged manually by a detachable handle. The full operating circuit is explained in
para.
2.7.
An essential difference between the solenoid and the
motor/spring closing systems is that the solenoid takes a very large current
during its quick stroke, necessitating heavy cable leads, whereas the motor
takes about five seconds to recharge the spring - that is, to deliver the same
energy - so that the motor draws far less current. The motors can, if the system requires it,
operate on a.c.
Both systems require a separate trip signal to actuate
the shunt-trip coil; this releases the closed mechanism and causes the breaker
to open under its own separate trip springs.
It can also be tripped mechanically by hand.
A number of complete housings, together with their
withdrawable circuit-breakers, can be assembled into a single switchboard, as
shown typically in Figure 2.5.
FIGURE 2.5
TYPICAL HIGH VOLTAGE
SWITCHBOARD
The panels, whose upper parts carry the local controls,
protective relays and indicating instruments, form a continuous
switchboard. The circuit-breakers are at
the bottom behind doors which can be opened for mechanical control of the
breaker or for withdrawing it.
The switchboard acts as an electrical ‘manifold’, with a
common set of busbars running the length of the board. In most offshore boards the busbars run along
the bottom, sometimes encapsulated in epoxy resin, and tee-offs are made from
them to the lower contacts of each circuit-breaker (Panels 1-8) and contactor
(Panels 10-13). This is shown in red in
Figure 2.5 for a typical high-voltage switchboard.
At a busbar transfer panel, such as Panel 9, the
copperwork run is changed from the bottom level (for the circuit-breakers) to
two levels for the tiers of contactors.
This arrangement is also shown in Figure 2.5. Sometimes (as here) use is made of the front
of a narrow transfer panel to accommodate extra relays.
At a bus-section panel, Panel 5, the bottom run on one
side passes into the bus-section circuit-breaker, and from its top contacts
back to the bottom level to feed the circuit-breakers on the other side. By studying Figure 2.5 it will be seen that,
even when the busbars on one side of a section breaker have been made safe for
maintenance by complete isolation and earthing down, the bus-section cubicle
may still have live copperwork on the other side of the circuit-breaker. Particular care is therefore necessary when
working on, or near to, bus-section cubicles.
Switchboards other than the one described and made by
other manufacturers, will differ in the detail of their busbar
arrangements. Nevertheless the
principles explained above will apply in all cases.
2.4 AIR BREAK CONTACTORS
Contactors (sometimes called Motor Switching Devices
(MSD) when used with motors) are generally smaller and lighter than
circuit-breakers operating on the same system because they carry less load current
and, more important, they do not have to break full system fault current. However they must be able to carry it for the specified time (3 sec
or 1 sec), to close onto it positively without bounce, arcing, or welding, and
to operate repeatedly.
For these reasons high-voltage contactors only occupy
half the space taken by the circuit-breaker, and they are usually mounted in
pairs, one above the other, in a panel the same size as for one
circuit-breaker. Four such contactor
panels can be seen on the right of the switchboard in Figure 2.5.
The contactor itself operates on the same principle as
the air-break circuit-breaker, with contacts in air and an arc chute. The closing mechanism is always
solenoid-operated, and particular attention is paid to the linkage to make it
robust and suitable for repeated operation, such as for motor starting.
Contactors may be ‘latched’ or ‘unlatched’. In the former case they hold-in by latch
after closing, and the closing solenoid is then de-energised. They require a separate trip signal to open
them by shunt-trip coil, as with the circuit-breaker.
Much more common, however, is the unlatched
contactor. It is held closed by its
closing solenoid, usually with reduced current through an economy
resistor. The solenoid remains energised
throughout. When it is desired to trip
the contactor, the solenoid is simply de-energised and the contactor ‘falls
off’. It also falls off if the supply to
the solenoid fails. Such contactors are
said to have an ‘inherent undervoltage’ feature, which means that, unlike the
latched type, they will open automatically if the operating voltage fails.
Because a contactor breaks normal currents but cannot
break a heavy fault current, it is usually backed up by fuses (see the manual
‘Electrical Protection’). These are a
set of high rupturing capacity (HRC) fuses in series. They are so chosen that, with currents in
excess of those which can be safely broken by the contactor, the fuses will
blow first, so
interrupting the current and leaving the contactor to
open on a dead circuit. These fuses,
which are quite large, are usually mounted at the bottom of the contactor unit,
which must be withdrawn in order to get at them.
FIGURE 2.6
HIGH VOLTAGE CONTACTOR UNIT
Figure 2.6 shows a typical half-height HV contactor
unit. The fuses can be seen at the
bottom. The contactor unit, with fuses,
is horizontally isolated and can be withdrawn on rails for servicing, maintenance
or fuse changing. A special carriage
with rails is required to withdraw an upper unit. The whole unit shown in Figure 2.6 is
withdrawable clear of the switchboard.
The HRC fuses are of the ‘trigger’ type. The blowing of any one fuse will mechanically
release the contactor, so ensuring a break in all three phases.
2.5 VACUUM CIRCUIT-BREAKERS AND CONTACTORS
Circuit-breakers and contactors which use vacuum
interrupters form another class of switching device. The principle upon which vacuum interrupters
control the arc and break heavy currents is described fully in Chapter 1. The paragraphs which follow describe how the
interrupters are actuated and how the circuit-breaker or contactor is
integrated into a switchboard panel.
The only important differences between a vacuum
circuit-breaker and a vacuum contactor are that the circuit-breaker has a much
larger rated breaking capacity and is latched, whereas the contactor is usually
unlatched. Apart from these features
and, of course, size, the description which follows applies to both.
FIGURE 2.7
VACUUM CONTACTOR
A typical vacuum interrupter
element, together with its operating mechanism, is shown in Figure 2.7. Figure 2.7(a) shows the interrupter in the
open position. The armature arm (green)
is held open by a compression spring, and the moving contact (yellow) is lifted
by a boss on it into the open position and held there. The vacuum area is coloured blue; it is
contained on its upper side by a bellows to take up the movement of the upper
contact.
When the closing coil is energised
it attracts the armature downwards away from the boss (Figure 2.7(b)). The moving contact is then free to move and
is forced downwards by atmospheric pressure, opposed only by the vacuum. It should be particularly noted that, with
this design, contact pressure is maintained by atmospheric pressure only.
To open the contacts the closing
coil is de-energised, the spring takes over and drives the armature
upwards. It strikes the boss and takes
the moving contact sharply with it against the atmospheric pressure, so returning
to the position of Figure 2.7(a). This
mechanism will be seen to be of the normal unlatched type, used when operating
as a contractor, which opens on the de-energising of the operating coil. When used as a circuit-breaker the motion
would be latched and a shunt-trip coil used to release it.
Other vacuum switches, particularly
vacuum circuit-breakers, have different types of mechanism and do not always
use atmospheric pressure. Those which
latch require a separate tripping coil which usually operates by breaking the
latching toggle.
Because vacuum interrupters are
sealed for life, there is no question of contact replacement. Since the vaporised metal is always
redeposited on the contacts, wear is in any case small. It can be detected by indicator or the use of
feeler gauges. If the wear of any one of
the set of three exceeds the manufacturer’s recommendation, all three
interrupters must be replaced since the small contact travel makes the
adjustment critical.
The 3-phase vacuum interrupter unit,
together with its operating mechanism and back-up fuses, is vertically isolated
within its own panel. The whole unit is
drawn downwards by operation of an external handle, as shown in Figure 2.8.
FIGURE 2.8
TYPICAL VACUUM CONTACTOR SWITCHBOARD
Interlocks are provided to prevent isolation unless the
interrupter is open. In those contactor
panels which feed motor circuits the act of downward isolation also
automatically puts an earth on the isolated feeder cable. In contactor panels which feed transformers
the feeder earth is separately applied by an external earthing handle which
cannot be moved until the interrupter unit is fully isolated.
A set of vacuum contactor panels, sometimes also with
vacuum circuit-breaker panels, can be assembled to form a complete switchboard,
as shown in Figure 2.8. Vacuum switch
panels are very narrow compared to the equivalent air-break circuit-breaker
panels and lend themselves well to very compact, space-saving switchboards.
2.6 SWITCHBOARD DISTRIBUTION
A high-voltage switchboard is an assembly point which
receives power from the HV generators or other sources, controls it and
distributes it. A common busbar system
runs through the board to which the power sources are connected through
switchgear. The busbars act as a
‘manifold’, and feeders are taken from it, through circuit-breakers or
contactors, to all power-consuming services such as transformers, motors or
interconnectors.
FIGURE 2.9
TYPICAL OFFSHORE HIGH VOLTAGE SYSTEM
Figure 2.9 shows, in diagram form, a typical air-break
HV switchboard. It is in fact the
diagram of the HV switchboard shown pictorially in Figure 2.5. It shows the two generator incomer breakers
(3 and 6), the bus-section breaker (5), four feeder breakers (1, 4, 7 and 8)
supplying very large motors which are too big for contactors, and one
interconnector breaker (2). On the right
are the four contactor panels. In Panel
9 (a bus transfer panel) the busbar splits into two - one for the high-level
and one for the low-level contactors.
There are three contactors (10, 12 and 13) feeding medium-sized motors
and one (11) feeding a transformer; all four contactors have back-up fuses.
2.7 CIRCUIT-BREAKER CONTROL
The closing mechanisms of
circuit-breakers met with on offshore and onshore installations are almost always
solenoid or motor/spring operated, as described in para. 2.3.3, and all
breakers have separate shunt-trip coils.
Solenoids are operated through their
own contactors, usually from a 110V d.c. supply. The control circuits are simple and need no
explanation here.
Motor/spring mechanisms are more
complicated. Their circuits require
switches and contacts to control the close and trip initiation and to ensure
the correct sequence of operation.
Circuits are also necessary for indication, for charging the closing
spring and for operating the closing release.
Auxiliary switches are therefore provided, mechanically linked to the
circuit-breaker mechanism. Also fitted
are carriage switches or isolating contacts which are operated by the movement
of the truck to the ‘Service’ or ‘Isolated’ positions.
FIGURE 2.10
TYPICAL CIRCUIT-BREAKER
CONTROL CIRCUIT (MOTOR/SPRING OPERATED)
A typical circuit-breaker
motor/spring control arrangement is shown, in diagram form, in Figure
2.10. Contacts are shown with the circuit-breaker
open and in the ‘Service’ position, all relays de-energised and the closing
spring discharged.
When the 110V d.c. supply is
connected, the spring charging motor runs; after the closing spring has been
charged and automatically latched, auxiliary limit contacts operate to stop the
motor and prepare the closing circuit.
Some circuit-breakers may only be
closed remotely by the manual operation of a switch at a remote electrical
control panel; others may be closed either remotely or by a local switch on the
switchgear panel, in which case a ‘Local/Remote’ selector switch is
fitted. The circuit illustrated in
Figure 2.10 is arranged for remote closing only. Once the spring is charged, operation of the
remote switch to the CLOSE position completes the closing circuit and energises
the closing coil; this releases the latch and the spring closes the
breaker. When the circuit-breaker has
closed, an auxiliary switch opens, disconnecting the closing coil, and at the
same time the motor, reconnected by the limit switch, runs to recharge and
latch the spring.
Normally the circuit-breaker is
tripped by operation of the remote switch; in addition a local ‘Emergency Trip’
pushbutton is fitted to the switchgear panel.
If a system fault causes the protection to operate, the trip relay
tripping contact closes. Closing any of
these tripping contacts energises the trip coil, releases the holding latch and
allows the breaker to open.
If the circuit-breaker closes onto a
faulty circuit it receives an immediate trip signal from the protection, which
causes it to trip; if the operator continued to hold the operating switch to
CLOSE, the circuit-breaker would ‘pump’ in and out until the control switch was
released. To prevent this, an
anti-pumping circuit is provided. When
the circuit-breaker closes, and while the control switch is still held to
CLOSE, an auxiliary switch completes a circuit to energise the anti-pumping
relay. The contacts of this relay change
over to break the closing coil circuit and complete a hold circuit for the
anti-pumping relay. Thus the breaker
will open if tripped by an immediate fault condition, but no further closing
operations can take place until the control switch has been released. This provides a ‘one-shot’ closing facility.
For maintenance it may be necessary
to close and trip the circuit-breaker by local control while it is disconnected
and isolated from the busbars. When the
truck is in the ‘Isolated’ position, carriage switch contacts operate to change
over the closing and tripping circuits from their normal connections to a local
test switch. This may now be used to
operate the circuit-breaker.
Auxiliary contacts operate lamps to
indicate when the circuit-breaker is open or closed. Additional contacts may provide control features
special to a particular circuit, such as the automatic start of standby motors,
load shedding, sequence starting or other special requirements.
Where solenoid closing is used
alone, its high d.c. current requires the closing solenoid itself to be
switched by a separate contactor.
Separate fuses are provided in each
switchgear cubicle for the closing and tripping supplies so that each may be
isolated without affecting the other, and to provide protection to each
auxiliary circuit appropriate to its loading.
The circuit-breaker motor/spring
control system shown in Figure 2.10 and described in this section is typical of
what may be found in many installations, but variations exist.
2.8 TRIP CIRCUIT SUPERVISION
There may be long periods of time
when circuit-breakers are not called upon to trip. It is vital however that, when the occasion
arises such as the onset of a fault, the trip circuit operates and the breaker
trips successfully. A ‘Trip Circuit
Supervision’ relay is provided on each circuit-breaker unit. It monitors the trip circuit and its power
supply continuously, both when the circuit-breaker is closed and also when it
is open.
A trip circuit supervision schematic
diagram is shown in Figure 2.11. The
trip circuit supervision relay consists of three elements: ‘a’, ‘b’ and
‘c’. The trip circuit is monitored by
passing a small current derived from the tripping supply through the trip coil
and all associated trip circuit wiring in series with the coils of relay ‘a’ or
‘b’ or both. This current is sufficient
to operate relays ‘a’ and ‘b’, even when they are connected in series, but,
being limited by resistors, is not high enough to trip the breaker. Relays ‘a’ and ‘b’ are energised individually
when the contacts across which they are connected are not closed. Relay ‘c’ is a hand-reset flag relay with
alarm contacts which are closed if the trip circuit is healthy, but they open
to give an alarm if it is not.
If the circuit-breaker is open, both
relays ‘a’ and ‘b’ are energised in series.
If the circuit-breaker is open but a trip initiation signal is present,
say from a hand-reset tripping relay, then relay ‘b’ alone is energised. When the circuit-breaker is closed, relay ‘b’
is de-energised and only relay ‘a’ monitors the trip circuit.
FIGURE 2.11
TRIP CIRCUIT SUPERVISION
If the trip supply fails or the breaker fails to open
when a trip signal is initiated, then both relays ‘a’ and ‘b’ are de-energised
and an alarm is initiated when relay ‘c’ releases. This happens when:
·
the trip
supply fails;
·
any part
of the trip circuit is open-circuited;
·
the
breaker fails to open;
·
the trip
circuit supervision relay auxiliary supply fails.
The opening of the contacts of relays ‘a’ and ‘b’ is
delayed by about 400ms to allow for transient dips in the 110V d.c. supply and
to allow time for the circuit-breaker to open without initiating an alarm.
2.9 FUSES
The only high-voltage fuses fitted in an HV switchboard
are those which form a back-up to a contactor (air-break or vacuum) and those
on the HV side of a voltage transformer.
All are of the high rupturing capacity (HRC) type.
The contactor fuses are of the open type but are
embodied in the contactor unit itself.
This forms adequate protection since it is necessary to isolate the
unit, and in the case of the air-break type to withdraw it, in order to gain
access to the fuses. They can be seen in
Figure 2.6.
Where fuses, whether HV or LV, are
used in series with a contactor, their purpose is to protect the contactor
itself against having to open on a fault current which is in excess of its
rating. Fuses used in this manner are
termed ‘back-up fuses’ and are selected with reference to the contactor’s own
inverse-time characteristic. This
process is fully described in the manual ‘Electrical Protection’.
Voltage transformer HV fuses form
part of the VT itself. The VT
compartment can only be opened after isolation, after which the fuses are
accessible. Although the VT fuses have a
very small current rating, they still have to be able to break a full-scale
short-circuit current if a fault should develop on the VT itself.
There are many low-voltage fuses in
the control and instrumentation circuits.
These are of the type described in Chapter 3 for LV switchgear.
2.10 CIRCUIT AND BUSBAR EARTHING DOWN
|
To ensure that a high-voltage circuit is safe to work on, it must be disconnected (isolated) from all sources of supply, and it must also be solidly earthed down. Earthing is carried out at the isolating switchgear.
FIGURE 2.12
FEEDER AND BUSBAR EARTHING
Earthing-down procedures vary from one type of
switchgear to another; the manufacturer’s operating instructions must be
consulted in each case.
Four examples of the use of switchgear for safety
earthing are shown in Figure 2.12. In
each case the circuit-breaker or contactor truck must be moved out of the
‘Service’ position before a permissive interlock key can be released which
permits earthing to take place.
Figures 2.12(a) and (b) show one
type of earthing system. In Figure
2.12(a) the feeder is earthed through an earthing switch that can only be
closed after the permissive interlock key has been inserted and operated. The permissive interlock key is released only
when the switchgear truck is either locked in the ‘Isolated’ position or
completely removed from the panel. For
busbar earthing the same switchgear uses a special earthing circuit-breaker
truck shown in Figure 2.12(b) which temporarily replaces the normal truck. Interlocks described below ensure that the
busbar cannot be earthed until it is disconnected from any possible source of
supply.
Figures 2.12(c) and (d) show a
different type of switchgear with ‘integral earthing’, where the busbar or the
feeder contacts on the circuit-breaker are moved mechanically to connect with a
set of earthed contacts mounted between the busbar and the feeder spouts. The busbar or feeder contacts can only be
moved after the appropriate permissive interlock key has been inserted into the
front panel of the switch-truck and operated.
This key, either busbar or feeder, is captive on the shutter operating
mechanism inside the switchgear panel and is only accessible when the truck is
removed. When either key is withdrawn,
the appropriate shutter will not open when the breaker truck is pushed in, so
preventing accidental access to live metal.
To earth a feeder, the busbar shutters must be immobilised, and vice
versa.
Where any earth is applied, a key is
released from the switchgear unit concerned, to be placed in a Lockout
Box. The earth cannot be removed until
the key is returned.
Before a section of busbars
is earthed down, all possible in-feeds must be disconnected. For example, one-half of a busbar system must
be isolated not only from its generator incomers but also from the other half
through the section breaker; also from any interconnectors and from any
transformer that could feed back into the busbar. To ensure this, the individual keys released
when all the possible in-feed breakers have been isolated are inserted into a
key-box. When all the keys are home, a
master key is released which permits the busbar earthing connection to be made
or the earthing switch to be inserted.
Full and detailed instructions for isolating and
earthing down are contained in ‘Standing Instructions Electrical’.
2.11 PANEL HEATERS
Each switchboard panel is fitted with an
anti-condensation heater; this is usually energised at 240V or 250V a.c. and
controlled either by a hand switch or by an auxiliary switch that connects the
heater when the circuit-breaker is open.
3 comments:
I never realized how much goes into switch board fitting! Your post has given me a newfound appreciation for electricians and the work they do. Thanks for sharing your knowledge!
I appreciate how your post breaks down the different aspects of power quality, from voltage fluctuations to harmonics. It provides a comprehensive understanding of the topic and offers actionable steps to mitigate power quality issues effectively.
Dealing with electrical issues in home appliances can be frustrating. Regular maintenance and understanding basic troubleshooting steps can help keep your appliances running smoothly.
Post a Comment